THE METERS

DESCRIPTION
The meter is a fully programmable ratemeter/ totalizer/ controller with six-digit resolution for totalizing input pulses or rate measuring.

Alphanumeric display prompts make it easy to program with front-panel buttons. You may use a personal computer to program the meter and monitor the display data using the RS-232 option. You may store the program setup in the nonvolatile memory for recall upon demand or at power-on.


The crystal timebase is electronically calibrated. There are no internal adjustments and calibration is done without opening the case. Available options include field-installable dual-relay option card, RS-232 and analog output cards.

FEATURES
The following is a list of features:
* 6-digit, single input * Display of any engineering unit
* Front-panel scaling * 0.5 Hz to 30 kHz frequency inputs
* Signal conditioner standard for low level inputs
* DIP switch input selection
* Sensor excitation of 5, 8.2 and 12.4 Vdc
* Front-panel programmable as rate meter or totalizer

For more detailed information on meter features, refer to Tables 6-1 and 6-2.

MAIN BOARD
Table 2-2 details information for the S2, S3, and S4 jumpers. The S2 jumper has 3 possible positions: A, B or C. Factory defaults are in bold and italics. Figure 2-1 illustrates where these jumpers are located on the main board.

Main Board Jumpers Table 2-2
Jumper/ Switch
Position: Installed
Description
S2
S2


S2-B

S2-C


Removed





Scale, offset, setpoints and decimal points are unlocked. All else is locked.

Everything is unlocked.

No lock-out, except for analog output parameters.

In the rate mode, meter shows "SPLO" and "SPHI" only (if the relay option board is installed). In the totalize mode, meter shows the OFFSEt, SPLO and SPHI - everything besides the relays are locked out. In either mode, the meter stores changes in the nonvolatile memory automatically.
S3
S3-A Removed
Enables front-panel buttons.
Disables front-panel buttons.
S4
S4 Removed
Enables RECALL button. Disables RECALL button.
* You must install S5 in either the A or B position.

Main Board
Figure 2-1. Main Board
Front of The Meter
Front Panel
Figure 2-2 Front-Panel

METER DISPLAY
Digital LED display
-.9.9.9.9.9. or 9.9.9.9.9.9. 6-digit 7-segment, 0.56" high LED display with programmable decimal point.


METER BUTTONS
RECALL Button
To initialize (hard reset) the meter, press the RECALL and RESET buttons simultaneously. The meter momentarily shows the program revision letter and mode (totalize or rate). The meter then shows the last stored (saved) program in the active (volatile) memory.

SET Button
Press this button to modify the flashing function, number value or decimal point (sub-menu only). For example, press the SET button to toggle between the totAL (totalize) and rAte (rate) modes. Once the correct function, number value or decimal point shows, press the MENU button to enter the change into the active (volatile) memory.

ADV Button
Press this button to show the sub-menus and values for a selected menu item. The meter shows values with left-most digit flashing. Press the ADV button to move the flashing item from left to right through the digital display and the SET button to change the flashing item's value.

MENU Button
Press this button to show main menu items (refer to Section 6 for more information). The meter does not show locked out (bypassed) items. The S2 and S3 jumpers determine lock out status.

RESET Button
Press this button to reset a latched alarm. Also, if you are in the totalize mode, press this button to reset the counter and begin counting from the offset. If you are in the setup menu (in either mode) the meter returns to the run mode and makes measure-ments with the latest updated menu items.

BACK OF THE METER
Table 2-3 shows S1 positions for different types of transducer signals and excitation. You may change default settings via the front-panel buttons.

S1 Dip Switch Positions Table 2-2 (Factory defaults are bold and in italics)
Transducer Type (Connect to TB2-2 & TB2-3)
S1 Positions
5 V CMOS S1-4
TTL S1-4, S1-1
NPN Open Collector S1-4, S1-7
PNP Open Collector S1-4, S1-6
NAMUR S1-4, S1-2, S1-6
Contact Closure to RTN S1-4, S1-7, S1-5
Contact Closure to EXC S1-4, S1-6, S1-5
Low Level Signal (Magnetic Pickup) S1-3
Low Level Signal When Average is Positive S1-3, S1-4
Excitation Output (Available on TB2-1)
5 V @ 50 mA max S1-2 Close
12.4 V @ 100 mA max* S1-1 Close
8.2 V @ 70 mA max* S1-1 Open and S1-2 Open
* Line voltage range is limited to 115/230 ▒10% for excitation currents more than 50 mA.

Back View of Meter
Figure 2-3 Back view of the meter.
Caution WARNING: Incorrect power input can damage the meter. (Factory defaults: bold)
Jumper/ Switch
Status
Description
S1-1
S1-2
S1-1
S1-2
S1-1
S1-2
Open
Closed
Open
Open
Closed
Open
Excitation output is set to 8.2 V

Excitation output is set to 12.4 V

Excitation output is set to 5.0 V
S1-3
Open
Closed
High hystersis = 1.5 V.
Low hystersis = 20 mV.
S1-4
Open
Closed
Threshold is normal.
Threshold is shifted to positive.
S1-5
Open
Closed
No low pass filter.
12 Hz low pass filter for contact closure.
S1-6
Open
Closed
No pull-down resistor.
1.0 Kohm pull-down resistor.
S1-7
Open
Closed
243K pull-up to +excitation.
3K pull-up resistor to excitation.
S1-8
Open
Closed
Trigger edge = Negative (high to low transition).
Trigger edge = Positive (low to high transition).
S1-9
Open
Closed
No signals internally connects to the input.
Twice line frequency signal internally connects to the input.
S1-10
Open
Closed
Detects an ac power loss. (Refer to Section 3.3) Maintains digital display during a dc power operation.
Help Price List Specifications Print Manual Manuals Home
 Home Home
 Table of Contents TOC  Back Back  Next Next